Technical Conditions and Performance Parameters
3.1 Power supply: The motor is three-phase AC, 380V (special order 660V, 440V or 220V), 50Hz (special order 60Hz); control line voltage 220V/50Hz (special order 60Hz); remote control voltage 24VDC.
3.2 Working environment:
3.2.1 Ambient temperature: -20-+60°C (special order-60-+80°C)
3.2.2 Relative temperature: ≤90% (at 25 °C)
3.2.3 Common and outdoor type for locations where there are no flammable/explosive and non-corrosive media; Ex-proof products are available in dI and dIIBT4. dI is suitable for non-mining working faces in coal mines; dIIBT4 is used in factories and is suitable for explosive gas mixtures in the T1-T4 group with environment IIA and IIB. (See GB3836.1 for details).
3.2.4 Protection level: Outdoor type and Ex-proof type are IP55 (customizable IP67).
3.3 Work system: for a short time of 10 minutes (can be customized for 30 minutes).
3.5 Main performance parameters
Type | Output torque(N.m) | Output speed(r/min) | Operation time for 90° turn(S) | Max stem diameter | With DZW type electric model | Rate current(KW) | Rated current(A) |
DQW10 | 100 | 1 | 15 | 28 | DZW5 | 0.12 | 0.57 |
DQW20 | 200 | 1 | 15 | 28 | DZW5 | 0.12 | 0.57 |
DQW30 | 300 | 1 | 15 | 28 | DZW5 | 0.12 | 0.57 |
DQW60 | 600 | 1 | 15 | 42 | DZW5 | 0.12 | 0.57 |
DQW90 | 900 | 0.75 | 20 | 42 | DZW10 | 0.25 | 1.03 |
DQW120 | 1200 | 0.75 | 20 | 42 | DZW10 | 0.25 | 1.03 |
DQW200 | 2000 | 0.5 | 30 | 60 | DZW15 | 0.37 | 1.38 |
DQW250 | 2500 | 0.5 | 30 | 60 | DZW15 | 0.37 | 1.38 |
DQW300 | 3000 | 0.5 | 30 | 60 | DZW20 | 0.55 | 2.2 |
DQW400 | 4000 | 0.5 | 30 | 60 | DZW20 | 0.55 | 2.2 |
DQW500 | 5000 | 0.5 | 30 | 70 | DZW30 | 0.75 | 2.62 |
DQW600 | 6000 | 0.5 | 30 | 80 | DZW30 | 0.75 | 2.62 |
DQW800 | 8000 | 0.45 | 35 | 100 | DZW45 | 1.1 | 4 |
DQW1000 | 10000 | 0.45 | 35 | 100 | DZW60 | 1.5 | 4.12 |
DQW1200 | 12000 | 0.45 | 35 | 100 | DZW60 | 1.5 | 4.12 |
DQW1600 | 16000 | 0.4 | 38 | 120 | DZW90 | 2.2 | 5.25 |
DQW2000 | 20000 | 0.4 | 38 | 120 | DZW90 | 2.2 | 5.25 |
DQW3200 | 32000 | 0.3 | 50 | 160 | DZW120 | 3 | 7.9 |
DQW4000 | 40000 | 0.3 | 50 | 160 | DZW180 | 4 | 8.87 |
DQW5000 | 50000 | 0.26 | 58 | 160 | DZW250 | 5.5 | 12.05 |
DQW6300 | 63000 | 0.26 | 58 | 180 | DZW350 | 7.5 | 15.6 |
DQW8000 | 80000 | 0.26 | 58 | 180 | DZW500 | 10 | 20.5 |
DQW12000 | 120000 | 0.24 | 63 | 220 | DZW500 | 10 | 20.5 |
DQW16500 | 165000 | 0.187 | 80 | 240 | DZW650 | 11 | 24 |
Installation Dimensions and Appearance Dimensions
DQW10~DQW3200 appearance dimensions
Type | Appearance dimensions | |||||||||
A1 | A2 | A3 | A4 | B1 | B2 | φD | ΦD1 | H1 | H2 | |
DQW10 | 80 | 98 | 289 | 570 | 86 | 321 | 196 | 250 | 110 | 526 |
DQW20 | ||||||||||
DQW30 | ||||||||||
DQW60 | ||||||||||
DQW90 | 100 | 115 | 371 | 590 | 102 | 425 | 230 | 365 | 126 | 638 |
DQW120 | ||||||||||
DQW200 | 125 | 150 | 371 | 590 | 120 | 425 | 300 | 365 | 160 | 704 |
DQW250 | ||||||||||
DQW300 | ||||||||||
DQW400 | ||||||||||
DQW500 | 160 | 195 | 371 | 590 | 115 | 425 | 358 | 365 | 197 | 770 |
DQW600 | ||||||||||
DQW800 | 160 | 195 | 515 | 810 | 115 | 516 | 358 | 470 | 197 | 885 |
DQW1000 | 200 | 248 | 515 | 810 | 135 | 516 | 430 | 470 | 215 | 895 |
DQW1200 | 200 | 248 | 515 | 810 | 135 | 516 | 430 | 470 | 215 | 895 |
DQW1600 | 200 | 248 | 540 | 830 | 135 | 660 | 430 | 550 | 215 | 930 |
DQW2000 | 250 | 292 | 540 | 830 | 170 | 660 | 540 | 550 | 270 | 1095 |
DQW3200 | 250 | 292 | 540 | 830 | 170 | 660 | 540 | 550 | 270 | 1095 |
DQW4000~DQW16500 appearance dimensions
Type | Appearance dimensions | ||||||||||
A1 | A2 | A3 | A4 | B1 | B2 | B3 | φD | ΦD1 | H1 | H2 | |
DQW4000 | 315 | 346 | 565 | 870 | 202 | 715 | 135 | 670 | 320 | 335 | 1325 |
DQW5000 | |||||||||||
DQW6300 | 315 | 346 | 770 | 1170 | 202 | 845 | 150 | 670 | 550 | 335 | 1430 |
DQW8000 | 380 | 380 | 770 | 1170 | 225 | 845 | 150 | 650 | 550 | 406 | 1486 |
DQW12000 | 602 | 410 | 770 | 1107 | 235 | 845 | 150 | 1050 | 550 | 525 | 2027 |
DQW16500 | 696 | 422 | 770 | 1107 | 285 | 845 | 150 | 1100 | 550 | 590 | 2188 |