Modbus RTU TCP Motorized Actuator

Optional Function Hart Communication Protocol HART communication uses a half-duplex communication method, which is characterized by the realization of digital signal communication on the existing analog signal transmission line, which is a transitional product during the transition from analog...

Optional Function

Hart Communication Protocol

HART communication uses a half-duplex communication method, which is characterized by the realization of digital signal communication on the existing analog signal transmission line, which is a transitional product during the transition from analog system to digital system, so it has a strong The market competitiveness has developed rapidly. HART stipulates a series of commands, which work according to the command mode. 

IQ25_06

Profibus Communication Protocol

PROFIBUS is an international, open field bus standard that does not depend on equipment manufacturers. The transmission speed of PROFIBUS can be selected in the range of 9.6kbaud ~ 12Mbaud and when the bus system is started, all devices connected to the bus should be set to the same speed. It is widely used in manufacturing automation, process industrial automation and building, transportation and other fields of automation. PROFIBUS is a field bus technology used for factory automation workshop-level monitoring and field device layer data communication and control.

IQ25_09

Bluetooth Communication

  1. Visualization

  2. Debugging convenient

  3. Operation and monitoring functions 

  4. Diagnostic function

  5. Download,save,upload all the information

  6. IQ25_15

  7. Protection Level---IP68

  8. IP is the abbreviation of Ingress Protection. The IP rating is the protection level against foreign objects in the electrical

  9. equipment enclosure. The source is  the International Electrotechnical Commission's standard IEC 60529, which was also adopted as the US national standard in 2004.

  10. imageimage

  11. The relevant test basis in China is GB 4208-2008/IEC 60529-2001 "Shell protection grade (IP code)" standard requirements, the conformity assessment test for the enclosure protection grade of various products; the highest detection grade IP68. Regular product inspection levels include IP23, IP44, IP54, IP55, IP65, IP66, IP67, IP68.


Main Technical Parameters

1.Intrinsic error: ±1%

2.Return difference: 1%

3.Dead zone: 0.5% ~ 10% adjustable

4.Damping force characteristic: dead-beat

5.Protection level: IP67(IP68 optional)

6.Environment temperature: -25℃ ~ +70℃ 

7.Relative Humidity: <95%(without condensation)

8.Power supply: 380Va.c(340V~440V), 50Hz/60Hz 3PH


The running performance of the actuator can be guaranteed in the case of the voltage error of ±10% and the frequency error of ±5 Hz. The actuator can start normally in the case of the maximum voltage drop of 15%, and can run as the normal speed.


Performance Data of FRYQ Single Phase On-off Type Actuator


Model

Revolving Speed

(rpm)

Torque

(Nm)

Voltage (V)

Phase (Ph)

Frequency

(Hz)

Power (kW)

Rated Current (A)

Duty

Weight

 (kg)

FRYIQ18

18

55

220

1

50

0.2

2.6

S2(10min)

30

24

50

220

1

50

0.2

2.6

S2(10min)

30

36

40

220

1

50

0.2

2.6

S2(10min)

30

48

35

220

1

50

0.2

2.6

S2(10min)

30

FRYQ25

18

210

220

1

50

0.9

9

S2(10min)

46

24

210

220

1

50

0.9

9

S2(10min)

46

36

170

220

1

50

0.9

9

S2(10min)

46

48

130

220

1

50

0.9

9

S2(10min)

46

FRYQ35

18

300

220

1

50

1.1

14

S2(10min)

69

24

300

220

1

50

1.1

14

S2(10min)

69

36

220

220

1

50

1.1

14

S2(10min)

69

48

160

220

1

50

1.1

14

S2(10min)

69

● FRYQ35 can not be used at 115 V. It is recommended that the actuator With the output speed of 144/ 173 rpm should not be used for the application of the directly installed valve.

● The rated torque is the maximum torque set in two directions. The maximum torque is 1.4 times to 2 times, depending on the valve speed and voltage.

● In case of using the maximum torque as required while exceeding 20% of the valve travel, please contact us.

Performance Data of IQ Three Phase Regulated Type Actuator

Model

Revolving Speed

(rpm)

Torque

(Nm)

Voltage (V)

Phase (Ph)

Frequency

(Hz)

Power (kW)

Rated Current (A)

Duty

Weight

 (kg)

FRYQ18

18

136

380

3

50

0.37

3.3

S4(30%)

30

24

108

380

3

50

0.37

3.3

S4(30%)

30

36

72

380

3

50

0.37

3.3

S4(30%)

30

48

54

380

3

50

0.37

3.3

S4(30%)

30

FRYQ25

18

400

380

3

50

1.1

5.8

S4(30%)

46

24

400

380

3

50

1.1

5.8

S4(30%)

46

36

298

380

3

50

1.1

5.8

S4(30%)

46

48

244

380

3

50

1.1

5.8

S4(30%)

46

FRYQ35

18

610

380

3

50

1.5

9.5

S4(30%)

69

24

610

380

3

50

1.5

9.5

S4(30%)

69

36

542

380

3

50

1.5

9.5

S4(30%)

69

48

474

380

3

50

1.5

9.5

S4(30%)

69

FRYQ40

18

1020

380

3

50

2.2

14.2

S4(30%)

190

24

1020

380

3

50

2.2

14.2

S4(30%)

190

36

845

380

3

50

2.2

14.2

S4(30%)

190

48

680

380

3

50

2.2

14.2

S4(30%)

190

FRYQ70

18

1490

380

3

50

3

18.2

S4(30%)

200

24

1490

380

3

50

3

18.2

S4(30%)

200

36

1290

380

3

50

3

18.2

S4(30%)

200

48

1020

380

3

50

3

18.2

S4(30%)

200

FRYQ90

18

2030

380

3

50

5.5

32

S4(30%)

200

24

2030

380

3

50

5.5

32

S4(30%)

200

36

1700

380

3

50

5.5

32

S4(30%)

200

48

1355

380

3

50

5.5

32

S4(30%)

200

FRYQ95

18

3000

380

3

50

7.5

42

S4(30%)

200

24

3000

380

3

50

7.5

42

S4(30%)

200

 

Main Technical Parameters

1.Intrinsic error: ±1%

2.Return difference: 1%

3.Dead zone: 0.5% ~ 10% adjustable

4.Damping force characteristic: dead-beat

5.Protection level: IP67(IP68 optional)

6.Environment temperature: -25~ +70 

7.Relative Humidity: 95%(without condensation)

8.Power supply: 380Va.c(340V~440V), 50Hz/60Hz 3PHIQ25_18

can be Epuiped with valvesIQ25_20